Home > News > Knowledge > Why can connecting multiple safety gates in series lead to fault masking?

Why can connecting multiple safety gates in series lead to fault masking?

Nov. 24, 2026

If opening any individual safety gate triggers a machine stop, does this mean the safety circuit has been fully verified?


When two sets of contacts from safety switches are connected in series to a safety relay, can we assume that each gate is independently monitored 

for the purpose of calculating Diagnostic Coverage (DC)?


Why might the evaluation of Diagnostic Coverage change for a system with four safety gates if the frequency of use, the number of operators, or 

the wiring configuration is altered?


Consider an automated system with four protective gates, each equipped with an electromechanical interlock switch featuring two contacts. The 

contacts are wired in series and connected to a single safety relay. Opening any one of the gates causes the equipment to stop. While this test verifies 

the stop response under normal operating conditions, it fails to adequately validate the system's diagnostic capability in the event of a fault.


When multiple gates share two series-connected signal paths, the monitoring logic only perceives the aggregate state of these circuits. The operation 

of one properly functioning gate can mask a fault that has already occurred at another gate—potentially even causing a previously detected fault to 

be inadvertently reset within the diagnostic logic. This phenomenon is known as "fault masking," which is the subject of this article.


I. How much information can two series-connected signal paths provide to the monitoring logic?


Let's examine a single-channel fault: suppose one contact on Gate A becomes welded shut. When the gate is opened, that channel remains closed 

(conductive), while the other channel opens as expected. The equipment may still stop, relying on the properly functioning channel; the monitoring 

logic might also detect the fault by identifying a discrepancy between the two signals.


However, if Gate B is opened simultaneously, both of its contacts will open, causing both series-connected circuits to enter an "open" (non-conductive) 

state. In this scenario, the discrepancy caused by the fault at Gate A is no longer reflected in the signals received by the monitoring logic.


Therefore, two distinct questions must be addressed: Can the safety function still be executed after a fault occurs? And can this fault be detected, 

triggering an appropriate response? While a dual-channel architecture provides redundancy, the mere presence of two input channels is not sufficient 

to guarantee that a fault at any individual gate will always be identifiable. Diagnostic Coverage (DC) measures the proportion of dangerous failure 

rates that are detected. It is not equivalent to the pass rate of a "door-opening/machine-stopping" test; for instance, successfully stopping the machine 

by opening any of four doors does not imply a DC of 100%. ISO 13849-1:2023, Section 6.1.5, provides specific requirements for determining DC.


II. ESPE – Two Types of Fault Masking, Distinguished by Whether the Fault Was Initially Detected


1. Direct Fault Masking: The fault remains unrevealed


Consider a scenario where one contact of Door A fails, remaining closed even when the door is opened. If Door B is opened first—breaking both series-

connected circuits—and then Door A is opened and closed while Door B remains open, the monitoring logic may continue to receive "open" signals from 

both channels. The inconsistency that would otherwise have been caused by the fault in Door A is effectively masked by the "open" state of Door B. Once 

Door A is closed again, followed by the closing of Door B, the inputs may return to a "normal" (closed) state, even though the physical fault in Door A persists.


ISO 14119:2024, Annex J.2.2, refers to this as "direct fault masking." The critical factors are the sequence in which the functional door and the faulty door 

are operated, and whether the monitoring logic can identify the anomaly based on the signals it ultimately receives.


2. Unintended Reset of a Fault: The fault was detected but subsequently masked


In another scenario, a fault in Door A causes an inconsistency between the two input channels, which the monitoring logic initially detects. Subsequently, 

another (functional) door is operated, causing a state change in the series-connected signals. In a flawed diagnostic scheme, this sequence could lead to 

an "unintended reset" of the detected fault state, potentially allowing the equipment to resume operation even though the original single fault remains 

present.


This corresponds to the "unintended reset of a fault" described in Annex J.2.3. Similar issues can also arise from cable faults, depending on the location 

of the fault relative to the specific interlocking device being operated. In this context, "reset" refers to the unintended clearing of a diagnostic fault 

state—even though the underlying issue with the contacts or cables remains unresolved. Furthermore, simply opening and closing a door does not 

necessarily clear a fault that has caused a safety relay to enter a locked (latched) state. Whether such an unintended reset occurs depends on the specific 

wiring, monitoring logic, and the conditions governing fault latching and resetting. The presence of a manual reset button does not negate the need 

for this assessment.


The common consequence of both mechanisms is that a dangerous fault may persist within the circuit. If an additional, undetected fault subsequently 

occurs, the existing redundancy could be further compromised, ultimately impairing the safety function.

Why can connecting multiple safety gates in series lead to fault masking?cid=51

III. ESPE – Determining Whether the Architecture Falls Within the Scope of Annex J


Clause 9.4 of ISO 14119:2024 requires consideration of the impact that fault masking—caused by the series connection of redundant contacts—has on the 

Diagnostic Coverage (DC). The maximum achievable DC must be evaluated in accordance with Annex J, which is a normative annex.


Annex J specifically addresses scenarios involving multiple interlocking devices with potential-free contacts (also referred to as "dry contacts" in 

GB/T 37157-2018), where both channels are physically connected in series to a monitoring logic unit responsible for diagnostics. The scope of Annex J is 

not limited solely to mechanically actuated position switches.


If individual doors are connected to separate safety inputs, or if interlocking devices with internal self-monitoring are used, the tables provided for the 

series connection of physical contacts cannot be applied simply because "multiple doors are connected to the same safety PLC." For configurations involving 

the series connection of electronic devices with self-diagnostics, OSSD (Output Signal Switching Device) outputs, or safety communication protocols, the 

evaluation must be based on the specific architecture and the manufacturer’s specifications.


Furthermore, if potential-free contacts from devices with different functions—such as non-safety-rated limit switches—are introduced into a chain of 

interlocking contacts, Annex J.4.4 clarifies that while fault masking may still occur, the probability of such masking cannot be estimated using the 

methods provided in this annex. One cannot simply treat an additional contact as "another door" and continue to use the tables.


IV. From the DC of an Individual Position Switch to the Upper Limit of DC in a Series Configuration (ESPE)


The approach outlined in Annex J.3 can be summarized as follows: first, determine the DC for each position switch based on the diagnostic measures 

employed (improving the design or diagnostics if necessary); then, use the criteria in J.4 to establish the maximum achievable DC for the specific series 

configuration. If the result still fails to meet design requirements, consider the improvement strategies provided in J.5.


This implies that the evaluation of a series configuration serves to establish a limiting condition. Even if the tables indicate that a "medium" level is 

permissible, one cannot simply upgrade a diagnostic measure—which can only be substantiated at a "low" level—to a "medium" level. The actual 

Diagnostic Coverage (DC) that can be claimed must not exceed the lower of two values: the DC supported by the diagnostic measures actually 

implemented, or the maximum achievable DC determined through a series-based evaluation.


According to ESPE (Electro-Sensitive Protective Equipment) standards, Annex J.4 provides two evaluation paths:


Simplified Method: Based on how the guards (doors/gates) are actually operated.


Table J.1 in section J.4.2 determines the maximum achievable DC based on the number of "frequently operated" guards, the number of other guards, 

and specific conditions. "Frequently operated" is defined by a specific criterion: an operating frequency of more than once per hour.


Beyond the number of guards, certain footnotes may alter the assessment: if more than one operator can independently open different guards, the 

count of "frequently operated" guards should be increased by one. Additionally, if the minimum distance between guards exceeds 5 meters, or if 

other guards cannot be reached directly from the position of a frequently operated guard, these conditions—listed in the table footnotes—allow for 

a downward adjustment (by one category) in the range used for "other" guards. Note that this is an adjustment of the evaluation category; one 

cannot simply exclude specific guards from the statistical count.


A special condition also applies: if "fault masking" is foreseeable—for instance, if multiple movable guards are opened simultaneously during normal 

operation or maintenance—the DC is limited to "none" under the simplified method. In this standard, "none" is a specific DC classification indicating 

a DC of less than 60%; it does not imply that the equipment lacks any diagnostic capabilities whatsoever.


Consequently, if the operational context changes after the equipment is commissioned—for example, shifting from "single-operator, occasional 

access" to "multi-operator, frequent intervention to clear jams"—the basis for the original DC evaluation may also change.


2. Standard Method: Incorporating wiring and diagnostic techniques into the assessment.


Section J.4.3 uses Table J.2 to determine the "Fault Masking" (FM) probability level. This level serves as an input for subsequent tables rather than 

representing a direct percentage of fault occurrence. Factors such as the number of guards, operating frequency, physical distance, accessibility, and 

the number of personnel remain relevant; if fault masking is foreseeable, the FM level is set to 3.


Subsequently, using Tables J.3 through J.5, the FM level is combined with factors such as wiring configuration, switch arrangement, signal evaluation 

methods, and cabling conditions to determine the maximum achievable DC. It is necessary to distinguish between star, branched, or ring wiring 

topologies; whether each door uses a "single-unit configuration" (one device providing two contacts) or a "redundant configuration" (two separate 

devices used for redundant channels); whether the signals are of the same polarity, opposite polarity, or dynamic; and whether the multi-core cable 

is protected against damage and whether it contains power-supply conductors intended for other purposes.


The mere fact that a single device possesses two contacts does not qualify it as a "redundant configuration" in this context. Furthermore, the 

presence of test pulses does not automatically preclude the possibility of fault masking; other conditions must also be evaluated.


Consider a hypothetical example to illustrate the difference between two signal paths: There are four doors—one operated twice per hour, and the 

other three operated very infrequently. There is only one operator for these doors; the criteria for reducing requirements based on distance or 

accessibility are not met; and there are no foreseeable scenarios for fault masking during normal operation or maintenance. Each door is set up in 

a "single-unit configuration" with two contacts wired in series within a ring topology. The multi-core cable lacks external protection against damage 

and does not contain power-supply conductors for other uses.


Under these specific constraints, the simplified method (Table J.1) yields a maximum Diagnostic Coverage (DC) of "low." Using the conventional 

method, Table J.2 provides an FM (Fault Masking) factor of 2; subsequently, Table J.3 indicates that static signals (whether of the same or opposite 

polarity) correspond to a "low" DC, while dynamic signals meeting the specified criteria correspond to a "medium" DC.


This discrepancy highlights that the conventional method accounts for diagnostic and wiring conditions that are not explicitly detailed in the 

simplified method. Even a "medium" rating represents only an upper limit; the actual diagnostic capability and other design parameters must still 

be verified. If the usage scenario or wiring configuration changes, a re-evaluation is required—the conclusions from this example cannot be 

applied to the new setup.


V. Why might an ESPE (Electro-Sensitive Protective Equipment) configuration be unsuitable, even if a higher PL (Performance Level) is calculated?


For the contact-series configuration discussed in Annex J—which lacks additional diagnostics—section J.4.1 limits the maximum achievable DC to 

"medium" and the maximum achievable Performance Level (PL) to PL d.


This specific limitation must be considered in conjunction with the quantitative evaluation required by ISO 13849-1. Even if the calculation results 

indicate a higher Performance Level (PL) after inputting more favorable component reliability parameters, the inherent limitations of a series-connected 

configuration cannot be bypassed. Conversely, the fact that a configuration is capped at PL d does not automatically imply that the current design 

has actually achieved PL d.


Evaluating a complete safety function requires considering factors such as Category, Mean Time to Dangerous Failure ($MTTF_d$), Average Diagnostic 

Coverage ($DC_{avg}$), Common Cause Failures (CCF), systematic failures, and safety-related software. The achieved PL must then be compared against 

the Required Performance Level ($PL_r$). The scope of the evaluation must encompass not only the interlocking inputs but also the logic processing 

and the output elements responsible for executing the stop function.


Note that $DC_{avg}$ is the weighted average of the Diagnostic Coverage (DC) for each component, calculated based on their respective dangerous 

failure rates; it is not a simple arithmetic mean of the individual DC values.


For designs that incorporate effective additional diagnostics, utilize independent safety inputs for each guard, or employ devices with internal 

self-diagnostics, the evaluation must be re-conducted based on the actual system architecture. It is incorrect to generalize the aforementioned upper 

limit—i.e., that "all series-connected safety guards are capped at PL d"—nor should one assume that simply replacing a component with a PL e-rated 

safety relay will resolve issues across the entire input chain.


For further insight into the relationship between calculation results and design documentation, please refer to the previously published article: "Why 

Does an Audit Find Issues Even When SISTEMA Calculates a PL d?"


VI. Improving Safety: Addressing Specific Faults and Diagnostic Capabilities (ESPE)


Appendix J.5 outlines several improvement strategies, including: adding contacts that connect to a monitoring device, supported by appropriate 

diagnostic routines; avoiding the physical series-connection of interlocking devices by providing independent safety inputs for each; and selecting 

interlocking devices that feature internal diagnostics and monitored outputs.


The common theme among these approaches is to either provide the diagnostic system with more detailed information regarding each interlocking 

device or to ensure effective monitoring occurs within the device itself. Simply adding a standard status feedback point—without the corresponding 

reliability data, diagnostic routines, and defined fault-response mechanisms—will not automatically improve the $DC$ of a safety function.


While cable protection measures may alter the evaluation parameters, any exclusion of specific faults must be justified based on the actual failure 

modes in question. Table D.4 of ISO 13849-2:2012 addresses various fault scenarios—including short circuits between conductors, short circuits 

between conductors and exposed conductive parts (or ground/protective bonding conductors), and conductor breakages—with distinct exclusion 

criteria for each. For instance, the exclusion of certain short-circuit faults within an electrical enclosure is contingent upon both the conductors and 

the enclosure itself meeting specific requirements; notably, the table provides no exclusion criteria for conductor breakages. Furthermore, measures 

such as "using shielded cables" or "routing cables inside an enclosure" are insufficient, on their own, to exclude all potential cable-related faults.


Verification must extend beyond the response to a normal shutdown to include behavior following a fault: which faults can be detected, whether the 

operation of another door might mask an existing fault, whether the fault state is appropriately maintained, and under what conditions the design 

permits a system reset. Any verification involving fault injection must be conducted under controlled conditions and in accordance with established 

safety procedures. Simply documenting a normal shutdown upon opening a door is insufficient to demonstrate these capabilities.


VII. Relevant National Standards (GB) and Version Considerations – ESPE


In China, two current recommended national standards (GB/T) are relevant:


GB/T 18831-2017, *Safety of machinery — Interlocking devices associated with guards — Principles for design and selection*, is identical to 

ISO 14119:2013. Section 8.6 of this standard addresses the issue of fault masking when interlocking devices are connected in series.


GB/T 37157-2018, *Safety of machinery — Evaluation of fault masking in series-connected interlocking devices with potential-free contacts*, is identical 

to ISO/TR 24119:2015 and focuses specifically on methods for evaluating fault masking. The Chinese terminology used in this text—such as "fault masking" ,

 "potential-free contacts" (), and "unintended reset of a fault" ()—is consistent with the terminology found in this official national standard.


ISO 14119:2024 has since incorporated the content of this technical report into its normative Annex J. While evaluation materials in Chinese are available 

domestically, the current standard GB/T 18831-2017 has not yet been updated to the 2024 version and does not include the new Appendix J. It is important

 to distinguish between the draft revision of GB/T 18831—which intends to adopt ISO 14119:2024—and the officially published standard. Meanwhile, 

ISO/TR 24119:2015 remains listed as "Published" on the official ISO website.


When conducting reviews using Chinese-language documentation, note a specific discrepancy: Section 6.3.2 of GB/T 37157-2018 (which incorporates the 

2015 technical report) stipulates that for the "conventional method," if fault masking is foreseeable, the Diagnostic Coverage (DC) must be set to "none." 

In contrast, ISO 14119:2024 (Appendix J, section J.4.3.2) does not retain this blanket restriction; instead, it requires setting the Fault Masking (FM) factor to 

3 (per Table J.2) and then determining the upper limit by referencing Tables J.3 through J.5. Consequently, the assessment results derived from the older 

national standard cannot be directly interchanged with those obtained using the conventional method in the 2024 version.


Another difference arises when contacts with different functions are mixed: Section 6.4 of both GB/T 37157-2018 and ISO/TR 24119:2015 state that 

because their respective methods cannot estimate the probability of fault masking, the DC should be considered "none." ISO 14119:2024 (Appendix J, 

section J.4.4) does not carry over this recommendation. However, the new version still explicitly clarifies that the probability estimation method provided 

in this appendix is not applicable to such mixed-contact configurations. Therefore, one cannot simply use the tables to determine the DC, nor should 

the removal of the aforementioned recommendation be interpreted as permission to assign a higher DC value. The corresponding European version is 

EN ISO 14119:2025; this, in combination with EN ISO 14119/A11:2026, has been included as a harmonized standard under the Machinery Directive 

2006/42/EC via Implementing Decision (EU) 2026/2015. This citation cannot be directly used as evidence of compliance under the new Machinery 

Regulation (EU) 2023/1230. For a comprehensive overview of the changes between versions, please refer to the article: "New Version of EN ISO 14119 

Added to the List of Harmonized Standards: What Are the Key Changes for Safety-Related Interlocking Devices?"


Determining the suitability of connecting multiple doors in series ultimately depends on the specific system architecture, operational usage, and diagnostic 

evidence. While the ability to stop the equipment by opening a door is one aspect of verification, other factors—such as whether a fault can be detected 

or if it might be masked by the operation of another door—also influence the evaluation of the Diagnostic Coverage (DC) and the overall safety function.


Status of Standards: The versions and official status mentioned above are accurate as of November 11, 2026. This text primarily references the technical 

content of ISO 14119:2024, with Chinese national standards (GB) cited to clarify the adoption relationship and ensure consistent terminology in Chinese.


ESPE Project Consulting

We provide services including compliance consulting for machinery exports and CE marking projects; risk assessment; technical documentation review 

and preparation; functional safety design reviews and PL/SISTEMA verification; safety assessments for in-service equipment; reviews and audits of safety 

retrofit plans; safety acceptance for new equipment; and training on machinery, electrical, and functional safety.